Practical Worked Example
Step-by-step practical problem and numerical calculation scenario.
Problem Statement
An industrial machine load operates on a single-phase equivalent AC feeder with a supply voltage of and draws a steady operating current of . Plant metering indicates an uncorrected lagging power factor of .
Calculate:
- The active real power () performing mechanical work.
- The total apparent power () demanded from the electrical feeder.
- The circulating reactive power () and fundamental phase displacement angle ().
Step-by-Step Solution
Step 1: Identify Input Parameters
- Supply Voltage ():
- Operating Current ():
- Power Factor (): (Lagging)
Step 2: Calculate Active Real Power ()
Active power represents the usable working rate of electrical energy conversion into heat, light, and shaft work:
The active working load is .
Step 3: Compute Total Apparent Power ()
Apparent power represents the total vector volt-ampere capacity that generators, transformers, and cables must deliver:
Alternatively, verifying via active power and power factor:
The total apparent demand is .
Step 4: Compute Reactive Power () and Phase Angle ()
Calculate the phase displacement angle between voltage and current:
Using the orthogonal AC power triangle relation ():
The reactive power exchanged between the magnetic fields of inductive windings and the generator is .
Step 5: Engineering Interpretation
- Capacity Utilization: At , only of the feeder capacity performs mechanical work. The remaining capacity sustains magnetic field flux in motor windings.
- Thermal Conductor Loading: Carrying to accomplish of work requires . If corrected toward unity (), the current required for the same work would drop to , reducing transmission heat loss by over .